6. SYSTEM DESIGN
INDOOR UNIT
8-2.
GENERAL RULES OF DRAIN PROCESS
Install the drain pipe with downward gradient (1/100 or more) and so there are no rises in the
●
pipe.
Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride) so
●
that there is no leakage.
Support the drain pipe with supporters each 5 to 7ft. (1.5 to 2.0m)
●
Do not perfrom air bleeding.
●
Always heat insulate the indoor side of the drain pipe.
●
When connecting the drain hose to the indoor unit, use the accessory band. (Except compact
●
wall mounted type and wall mounted type)
COMPACT CASSETTE TYPE
PVC pipe
(Local
arrangement)
(3/4 inch)
11-13/16 (300) or less
M
a
x. 27
-9
/1
6 (
7
0
0
)
Attached band
drain hose
(accessory)
Downward
gradient 1/100
or more
Horizontal or
upward gradient
5 to 7ft.
(1.5 to 2.0m)
Unit: in. (mm)
Hanging fitting
Downward gradient
1/100 or more
Air bleeding
Rise
Trap
Not good
CAUTION
Drain lift-up pipe restrictions:
●
(1) Lift-up height ≤ 27-9/16in. (700mm) (from ceiling)
(2) Drain hose (pipe) length ≤ 11-13/16in. (300mm) (between indoor unit and lift-up pipe)
When a dimensions exceed the above restrictions will cause water leakage.
●
- (06 - 105) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...