6. SYSTEM DESIGN
PIPE SIZE
2-3.
PIPE DIAMETER, RECOMMENDED MATERIAL AND WALL THICKNESS
Nominal Diameter
(in)
1/4"
3/8"
1/2"
5/8"
3/4"
Outside Diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Material
JIS H3300 C1220T-O or equivalent *1
Wall Thickness *2
(mm)
0.8
0.8
0.8
1.0
1.2
*1: Allowable tensile stress ≥ 33 (N/mm
2
)
*2: Endurance pressure of the pipe must be 609 psi (4.2 MPa).
Please select the pipe size in accordance with local rules.
PIPE SIZE SELECTION
Branch box 1
(Primary)
First
Separation
tube
Outdoor unit
Indoor units
Branch box 2
(Secondary)
Branch box 3
(Secondary)
Pipe size
table"A"
Pipe size
table"B"
Pipe size
table"C"
Pipe size
table"D"
Second
Separation
tube