6. SYSTEM DESIGN
CONTROLLER CABLE WIRING
4-4.
WIRING SPECIFICATIONS
Model type
Connection to
Wire
Cable size
Specification
Central remote
controller
Branch box
Remote controller
cable
22 AWG
Sheathed PVC cable Polar
3core
Wired Remote
Controller
Indoor unit
Remote controller
cable
22 AWG
Simple Remote
Controller
Indoor unit
IR Receiver Unit
Indoor unit
Connection cable
-
[16ft. (5m) cable attached]
Caution
Install in accordance with local rules and regulations.
●
Never bundle the power supply cable and controller cable together. Bundling these cords together
●
will cause misoperation.
Always ground for shilded cable both end.
●
For detail specification and connection, please refer to "5 Control system".
●