3. OUTDOOR UNIT & BRANCH BOX
SAFETY DEVICES
9.
OUTDOOR UNIT
9-1.
Safety device
AOU48RLXFZ
Fuse
Main PCB
AC 250V 3.15A
INV PCB
DC 400V 5A
Filter
AC 250V 10A
AC 250V 3.15A
Protector
Filter
AC 500V 50A
Compressor Protector
Overcurrent protection -
Temperature protection Off : 239°F (115°C) On : 158°F (70°C)
High Pressure Protection
Off : 609psi (4.2MPa) On : 464psi (3.2MPa)
Low Pressure Protection
Off : 7.25psi (0.05MPa)
BRANCH BOX
9-2.
Safety device
UTP-PU03A, UTP-PU03B
Fuse
PCB
AC 250V 3.15A x 2
AC 250V 10A x 1