6. SYSTEM DESIGN
FRESH AIR CONTROL OUTPUT
Compact Cassette
Slim Duct
Comapct Wall
Mounted
Wall Mounted
Connector
CN6
CN6
-
-
A signal linked to air conditioner indoor fan ON can be output.
* However, signal becomes OFF during cold air prevention control operation.
Circuit diagram example
Relay spec.:
Rated 12V DC, 50mA to less.
Field supply
Indoor
control PC board
Connector
1
12 V
on/off
2
Signal
Relay
power
supply
Ex.) Fan
Connected unit
Ex.) Relay unit
*33ft.
(10m)
* Make the distance from the PC board to the connected unit within 33ft. (10m).
ON
OFF
Operation
Stop
Indoor fan
Output signal
Parts (Optional)
Compact Cassette
Slim Duct
Comapct Wall
Mounted
Wall Mounted
Parts name
External control set External control set
-
-
Model name
UTD-ECS5A
UTD-ECS5A
-
-
* The wire (fresh air output) for connecting the fresh air intake kit (optional parts) is attached to the fresh air intake kit
and, therefore, does not have to be purchased separately.
- (06 - 102) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...