3. OUTDOOR UNIT & BRANCH BOX
INSTALLATION SPACE
3.
OUTDOOR UNIT
3-1.
Caution
The installation space shown in the following examples is based on an ambient temperature under
●
cooling operation of 95 °F DB (35 °C DB) at the air intake of the outdoor unit.
Provide more space around the air intake than shown in the examples if the ambient temperature
exceeds 95 °F DB (35 °C DB) or if the thermal load of all of the outdoor units exceeds the capacity.
Consider the transportation route, installation space, maintenance space, and access, and install
●
the unit in a location with sufficient space for the refrigerant piping.
Observe the installation space specifications that are shown in the figures.
●
Provide the same space for the air intake at the rear of the outdoor unit.
If the installation is not performed according to the specifications, it could cause a short circuit and
result in a lack of operating performance.
As a result, the outdoor unit might easily be stopped by high-pressure protection.
Air intake
Rear view
Installation methods not shown in the following examples are not recommended.
●
Performance may drop significantly.
SINGLE OUTDOOR UNIT INSTALLATION
3-1-1.
WHEN THE UPWARD AREA IS OPEN
Unit : inch (mm)
Obstacles at rear only
Obstacles at rear and sides only
5-29/32 (150)
7-7/8 (200)
7-7/8 (200)
11-13/16 (300)
Obstacles at front only
Obstacles at front and rear only
39-3/8 (1000) or more
39-3/8 (1000) or more
5-29/32 (150)
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD
AREA
Obstacles at rear and above only
Obstacles at rear, sides, and above
only
11-13/16 (300)
Max. 19-11/16 (500)
39-3/8 (1000)
59-1/16 (1500)
9-27/32 (250)
9-27/32 (250)
19-11/16 (500)
Max. 19-11/16 (500)
- (03 - 06) -
OU
TDOOR
UNITS
OU
TDOOR
UNITS
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...