6. SYSTEM DESIGN
FUNCTION DETAILS
5-6.
Functions
Compact
cassette
Slim duct
Compact wall
mounted
Wall
mounted
1) Filter sign
2) Ceiling height
-
-
-
3) Outlet directions
-
-
-
4) Static pressure
-
-
-
5) Cooler room temperature correction
6) Heater room temperature correction
7) Auto restart
8)
Indoor room temperature sensor
switching function
9) Remote controller signal code
10) External input control
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time
setting for the filter sign display interval in the table below according to the amount of dust or
debris in the room. If you do not wish the filter sign to be displayed, select the setting value for
"No indication".
(
... Factory setting)
Setting description
Function number
Setting value
Standard
11
00
Long interval
01
Short interval
02
No indication
03
The filter sign interval time is different according to Indoor unit type as follows.
Setting description
Comapact
Cassette
Slim Duct
Compact Wall
Mounted
Wall Mounted
Standard
2500 hours
400 hours
Long interval
4400 hours
1000 hours
Short interval
1250 hours
200 hours
2) Ceiling height
Select the setting values in the table below according to the height of the ceiling.
(
... Factory setting)
Setting description
Function number
Setting value
Standard [9ft. (2.7m)]
20
00
High ceiling [10ft. (3.0m)]
01
3) Outlet directions
Select the setting values in the table below for using a 3-way outlet.
(
... Factory setting)
Setting description
Function number
Setting value
4-way
22
00
3-way
01
- (06 - 68) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...