6. SYSTEM DESIGN
EXTERNAL OUTPUT
7-1-2.
ERROR STATUS OUTPUT
An air conditioner error status signal is produced when a malfunction occurs.
•
Circuit diagram example
1) Power supply
●Voltage (Chart sign=Vcc) : DC 24V or less
2) Load
● Load : DC 500mA or less is recommended
Signal
Outdoor unit
control PC board
Connected unit
Connector
1
2
Field supply
*33ft. (10m)
Vcc
+
+
-
Load
Vcc
Power
supply
* Make the distance from the PC board to the connected unit within 33ft. (10m).
Error
Normal
ON
OFF
Error status
Output signal
Parts (Optional)
Parts name
External connect kit
Model name
UTY-XWZXZ3
- (06 - 95) -