6. SYSTEM DESIGN
EXAMPLE 4
1
2
3
a
b
d
f i
l
e
c
Outdoor unit
Separation
tube
Branch box
Branch box
Branch box
Separation
tube
Indoor unit
Indoor unit
Indoor unit
(18000Btu)
(18000Btu)
(24000Btu)
System configuration
(Indoor units)
1
2
3
4
5
6
7
8
Total Capacity
(Btu)
Model name
ASU18
ASU18
ASU24
60000
Capacity (Btu)
18000
18000
24000
Capacity ratio
(Total indoor unit capacity) / (Total outdoor unit capacity)
= (60000) / (48000) = 125.0% (Within 80% to 130%)
Selection of separation tube
Model
Q'ty
UTP-SX248A
2
Selection of branch box
Model
Q'ty
UTP-PU03A (primary)
1
UTP-PU03B (secondary)
2
Selection of pipe size
a
b
c
d
e
f
g
Liquid pipe size
in. (mm)
3/8
(9.52)
3/8
(9.52)
3/8
(9.52)
3/8
(9.52)
3/8
(9.52)
1/4
(6.35)
Gas pipe size
in. (mm)
5/8
(15.88)
5/8
(15.88)
5/8
(15.88)
5/8
(15.88)
5/8
(15.88)
1/2
(12.70)
Pipe length
ft (m)
23
(7)
59
(18)
59
(18)
16
(5)
16
(5)
39
(12)
h
i
j
k
l
m
Liquid pipe size
in. (mm)
1/4
(6.35)
1/4
(6.35)
Gas pipe size
in. (mm)
1/2
(12.70)
5/8
(15.88)
Pipe length
ft (m)
39
(12)
39
(12)
- (06 - 24) -
SY
S
T
E
M
DE
SIGN
SY
S
T
E
M
DE
SIGN
Summary of Contents for ARU12RLF
Page 3: ...1 GENERAL INFORMATION DTR_BMU001E_03 CHAPTER01 2010 08 25 Hybrid Flex Inverter System ...
Page 18: ...2 MODEL SELECTION DTR_BMU001E_04 CHAPTER02 2010 10 04 Hybrid Flex Inverter System ...
Page 38: ...3 OUTDOOR UNIT BRANCH BOX Hybrid Flex Inverter System DTR_BMU001E_04 CHAPTER03 2010 10 04 ...
Page 58: ...4 INDOOR UNITS Hybrid Flex Inverter System DTR_BMU001E_05 CHAPTER04 2010 11 12 ...
Page 116: ...5 CONTROL SYSTEM DTR_BMU001E_04 CHAPTER05 2010 10 04 Hybrid Flex Inverter System ...
Page 152: ...6 SYSTEM DESIGN DTR_BMU001E_04 CHAPTER06 2010 10 04 Hybrid Flex Inverter System ...
Page 287: ...7 OPTIONAL PARTS Hybrid Flex Inverter System DTR_BMU001E_03 CHAPTER07 2010 08 25 ...