6. SYSTEM DESIGN
STOP OPERATION MODE
It is possible to switch to Batch stop or Emergency stop and Normal operation by using external
•
input.
Circuit diagram example
Contact capacity : 24VDC or more, 10mA or more.
Outdoor unit
control PC board
Connector
1
2
Signal
Field supply
*33ft. (10m)
Connected unit
Ex.) Switch
* Make the distance from the PC board to the connected unit within 33ft. (10m).
Use the following parts and construct a circuit as shown above.
•
Set the "Batch stop" or "Emergency stop" pattern, refer to "5.FUNCTION SETTING"
•
When function setting is "Batch stop" mode
●
Remote controller
On
On
Input signal
On
Off
Air conditioner
Operation
Stop
Command
Batch stop
Normal
Remote control
operation validity
- (06 - 93) -