5. Diagnostics and error handling
5−24
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 6 Valve error
CPX error group 106
(CPX−MMI: [Error in valve])
No.
Message
Cause/description
Error handling
Type
1)
60
Communication with valve
disturbed or valve not
available
Only the position measur
ing system/sensor inter
face was found at
switch−on. The valve was
not detected.
·
Check the lines to the
valve.
·
Replace the valve.
Error level: F2
Reset: N
Communication between
CMAX and the valve was
interrupted.
·
Check the lines of the
axis string, valve and
sensor step−by−step and
exchange, if necessary.
61
Valve hardware is defec
tive
The valve signals a hard
ware error.
·
Replace the valve.
Error level: F2
Reset: N
Error while initialising the
valve.
·
Exchange the valve,
check the firmware
version of CMAX.
62
Overtemperature at valve
The valve signals overtem
perature. (Ambient tem
perature too high).
·
Make sure there is
sufficient cooling.
Error level: F2
Reset: F
63
Valve jammed
The valve piston does not
move as expected.
·
Replace the valve.
·
Also check the air
quality (5 filter and
dry air).
Error level: F2
Reset: F
64
Valve load voltage outside
tolerance range (under−
voltage)
The valve signals a load
voltage which is too low.
Either the line between
CMAX and the valve is
defective or the valve is.
·
Check the cables on the
axis string.
·
Check the valve and ex
change, if necessary.
Error level: F2
Reset: F
1)
For the error level and reset type, see section 5.2.3.
Summary of Contents for CPX-CMAX-C1-1
Page 2: ......
Page 22: ...Contents and general safety instructions XX Festo P BE CPX CMAX SYS EN en 0908NH...
Page 23: ...CMAX system overview 1 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 1...
Page 31: ...Fitting and pneumatic installation 2 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 2...
Page 60: ...2 Fitting and pneumatic installation 2 30 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 61: ...Electrical installation 3 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 3...
Page 79: ...Commissioning 4 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 4...
Page 122: ...4 Commissioning 4 44 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 123: ...Diagnostics and error handling 5 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 5...
Page 163: ...Technical appendix A 1 Festo P BE CPX CMAX SYS EN en 0908NH Appendix A...
Page 176: ...A Technical appendix A 14 Festo P BE CPX CMAX SYS EN en 0908NH...