5. Diagnostics and error handling
5−11
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 1 Execution error
CPX error group 101
(CPX−MMI: [Execution error])
Continued
No.
Message
Cause/description
Error handling
Type
1)
16
Dynamic Identification
failed
Incorrect mass was
parameterised or trans
ferred to parameter 2.
2)
·
Check the mass and
data.
Error
level: F1
Reset: R
Too much mechanical
backlash in the system.
·
Check the system
structure.
Design not stable
enough.
·
Check the system
structure.
Used tubes are too long.
·
Place the valve closer
to the drive.
Compressed air is not
sufficiently stable.
·
Check the pressure
supply.
17
Identification not yet
executed
Static identification was
not executed at start of
record, during direct
mode or homing.
·
Static identification
executed
Error level: W
Reset: F
18
Clamping unit is still acti
vated, operation enable
not possible
Operation enable
was granted
(CCON.STOP = 1),
although the clamping
unit was not yet re
leased.
·
Cancel operation en
able.
·
Release clamping unit.
Error level: W
Reset: F
19
Invalid change of
operating mode
Changing between re
cord select and direct
modes during an active
positioning job
(SPOS.MC=0).
·
Switch only after
completed position
ing job
(SPOS.MC = 1)
Error
level: F1
Reset: R
Changing between re
cord select and direct
modes and commission
ing or parametrising op
erating mode while oper
ation enable is active
(CCON.STOP=1).
·
Only switch when
status is stopped".
Set CCON.STOP
= 0 and wait for
SCON.OPEN = 0 and
SPOS.MC = 1
1)
For the error level and reset type, see section 5.2.3.
2)
Parameter 2: Byte 4 ... 8 in commissioning operating mode.
Summary of Contents for CPX-CMAX-C1-1
Page 2: ......
Page 22: ...Contents and general safety instructions XX Festo P BE CPX CMAX SYS EN en 0908NH...
Page 23: ...CMAX system overview 1 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 1...
Page 31: ...Fitting and pneumatic installation 2 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 2...
Page 60: ...2 Fitting and pneumatic installation 2 30 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 61: ...Electrical installation 3 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 3...
Page 79: ...Commissioning 4 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 4...
Page 122: ...4 Commissioning 4 44 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 123: ...Diagnostics and error handling 5 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 5...
Page 163: ...Technical appendix A 1 Festo P BE CPX CMAX SYS EN en 0908NH Appendix A...
Page 176: ...A Technical appendix A 14 Festo P BE CPX CMAX SYS EN en 0908NH...