5. Diagnostics and error handling
5−25
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 6 Valve error
CPX error group 106
(CPX−MMI: [Error in Valve])
Continued
No.
Message
Cause/description
Error handling
Type
1)
65
Valve operating voltage
outside tolerance range
(undervoltage)
The valve signals an
operating voltage which is
too low. Either the line be
tween CMAX and the valve
is defective or the valve is.
·
Check the cables on the
axis string.
·
Check the valve and
exchange, if necessary.
Error level: F2
Reset: F
66
Overload at digital output
of valve
The valve signals an over
load at the digital output.
·
Check the connections
and correct.
Error level: F2
Reset: F
67
Overload on 24V voltage
output of the valve
The valve signals an over
load at the voltage output.
·
Check the circuitry and
correct.
Error level: F2
Reset: F
68
Warning: Overtemperature
at valve
The valve signals a high
operating temperature.
(Ambient temperature too
high).
·
Make sure there is
sufficient cooling.
Error level: W
Reset: F
1)
For the error level and reset type, see section 5.2.3.
Summary of Contents for CPX-CMAX-C1-1
Page 2: ......
Page 22: ...Contents and general safety instructions XX Festo P BE CPX CMAX SYS EN en 0908NH...
Page 23: ...CMAX system overview 1 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 1...
Page 31: ...Fitting and pneumatic installation 2 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 2...
Page 60: ...2 Fitting and pneumatic installation 2 30 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 61: ...Electrical installation 3 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 3...
Page 79: ...Commissioning 4 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 4...
Page 122: ...4 Commissioning 4 44 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 123: ...Diagnostics and error handling 5 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 5...
Page 163: ...Technical appendix A 1 Festo P BE CPX CMAX SYS EN en 0908NH Appendix A...
Page 176: ...A Technical appendix A 14 Festo P BE CPX CMAX SYS EN en 0908NH...