9.2.2.2. Interlock (INTERLOCK)
The input status of a movable guard or a safety door is checked by the INTERLOCK function block. If the movable guard or
the safety door is opened, the OUTPUT output is "0" (FALSE), otherwise the OUTPUT output is "1" (TRUE).
Figure 84: Interlock
Parameter
Input Type:
Ì
Double NC – makes it possible to connect components with two normally closed contacts.
Ì
Double NC-NO – makes it possible to connect components with one normally closed contact and one normally open
contact.
Important!
¨
Connect inactive input (OUTPUT output is "0" (FALSE)) as follows:
Ì
NO contact to terminal that has been assigned to the input IN1.
Ì
NC contact to terminal that has been assigned to the input IN2.
Manual Reset: If selected, a reset can be requested on every activation of the movable guard or the safety door. Otherwise
the activation of the output will correspond directly to the input conditions.
There are two types of reset: "Manual" and "Monitored". On the selection of the manual reset, the system only checks the
signal transition from 0 to 1. With the monitored reset the double transition from 0 to 1 and then back to 0 is checked.
Manual
Monitored
Figure 85: Interlock manual/monitored reset
Figure 86: Connection example, interlock