23
2121331-04-04/19 (Translation of the original operating instructions)
Operating Instructions
Modular Safety Control System MSC
EN
5.3.4.1. Module AZ-FO4
TERMINAL
SIGNAL
TYPE
DESCRIPTION
VERSION
1
24 VDC
-
Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input (
"type B"
as per EN 61131-2)
3
NODE_SEL1
Input
Input (
"type B"
as per EN 61131-2)
4
GND
-
Power supply 0 VDC
-
5
REST_FBK1
Input
Feedback loop/restart 1
Input as per EN 61131-2
6
REST_FBK2
Input
Feedback loop/restart 2
Input as per EN 61131-2
7
REST_FBK3
Input
Feedback loop/restart 3
Input as per EN 61131-2
8
REST_FBK4
Input
Feedback loop/restart 4
Input as per EN 61131-2
9
A_NO1
Output
Normally open contact channel 1
10
B_NO1
Output
11
A_NO2
Output
Normally open contact channel 2
12
B_NO2
Output
13
A_NO3
Output
Normally open contact channel 3
14
B_NO3
Output
15
A_NO4
Output
Normally open contact channel 4
16
B_NO4
Output
Table 11: Module AZ-FO4
5.3.4.2. Module AZ-FO4O8
TERMINAL
SIGNAL
TYPE
DESCRIPTION
VERSION
1
24 VDC
-
Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input (
"type B"
as per EN 61131-2)
3
NODE_SEL1
Input
Input (
"type B"
as per EN 61131-2)
4
GND
-
Power supply 0 VDC
-
5
REST_FBK1
Input
Feedback loop/restart 1
Input as per EN 61131-2
6
REST_FBK2
Input
Feedback loop/restart 2
Input as per EN 61131-2
7
REST_FBK3
Input
Feedback loop/restart 3
Input as per EN 61131-2
8
REST_FBK4
Input
Feedback loop/restart 4
Input as per EN 61131-2
9
A_NO1
Output
Normally open contact channel 1
10
B_NO1
Output
11
A_NO2
Output
Normally open contact channel 2
12
B_NO2
Output
13
A_NO3
Output
Normally open contact channel 3
14
B_NO3
Output
15
A_NO4
Output
Normally open contact channel 4
16
B_NO4
Output
17
SYS_STATUS1
Output
Programmable digital output 1
PNP active high
18
SYS_STATUS2
Output
Programmable digital output 2
PNP active high
19
SYS_STATUS3
Output
Programmable digital output 3
PNP active high
20
SYS_STATUS4
Output
Programmable digital output 4
PNP active high
21
SYS_STATUS5
Output
Programmable digital output 5
PNP active high
22
SYS_STATUS6
Output
Programmable digital output 6
PNP active high
23
SYS_STATUS7
Output
Programmable digital output 7
PNP active high
24
SYS_STATUS8
Output
Programmable digital output 8
PNP active high
Table 12: Module AZ-FO4O8