8. Technical data
8.1. General system settings
8.1.1. Safety-related parameters
Parameter
Value
Standard
PFH
D
See tables with technical data for the related module
EN IEC 61508:2010
SFF
99.8 %
HFT
1
Safety standard
Type B
SILCL
3
EN IEC 62061:2005
TYPE
4
EN IEC 61496-1:2013
PL
e
EN ISO 13849-1
EN IEC 62061:2005
DC
avg
High
MTTF
D
(years)
30 – 100
Category
4
Device mechanical life
20 years
Degree of contamination
2
8.1.2. General data
Number of inputs max.
128
Number of outputs max.
16, dual-channel
Number of extension modules max.
14
Number of extension modules of the same type max.
4
Operating voltage
24 VDC ±20 % / class II supply (LVLE)
Overvoltage category
II
Digital INPUTS
PNP active high (EN 61131-2)
OSSD (MSC-CB, FI8FO2, AC-FO2, AC-FO4)
PNP active high – 400 mA at 24 VDC max. (per OSSD)
Digital OUTPUTS
PNP active high – 100 mA at 24 VDC max.
Response time (ms)
This response time is dependent on the following parameters:
1) Number of extension modules installed
2) Number of operators
3) Number of OSSD outputs
The correct response time is calculated by the software EUCHNER Safety Designer
(see project report).
Fault reaction time (ms)
The fault reaction time corresponds to the reaction time, except on SPM modules
with an encoder/proximity switch interface.
In this case the fault reaction time is 2 s.
Base unit
10.6 – 12.6
+ T
Input_filter
MSC-CB + 1 extension module
11.8 – 26.5
+ T
Input_filter
MSC-CB + 2 extension modules
12.8 – 28.7
+ T
Input_filter
MSC-CB + 3 extension modules
13.9 – 30.8
+ T
Input_filter
MSC-CB + 4 extension modules
15 – 33
+ T
Input_filter
MSC-CB + 5 extension modules
16 – 35
+ T
Input_filter
MSC-CB + 6 extension modules
17 – 37.3
+ T
Input_filter
MSC-CB + 7 extension modules
18.2 – 39.5
+ T
Input_filter
MSC-CB + 8 extension modules
19.3 – 41.7
+ T
Input_filter
MSC-CB + 9 extension modules
20.4 – 43.8
+ T
Input_filter
MSC-CB + 10 extension modules
21.5 – 46
+ T
Input_filter
MSC-CB + 11 extension modules
22.5 – 48.1
+ T
Input_filter
MSC-CB + 12 extension modules
23.6 – 50.3
+ T
Input_filter
MSC-CB + 13 extension modules
24.7 – 52.5
+ T
Input_filter
MSC-CB + 14 extension modules
25.8 – 54.6
+ T
Input_filter
MSC-CB > module connection
Proprietary 5-way bus (MSCB) from EUCHNER
Connection cable cross-section
0.5 – 2.5 mm
2
/ AWG 12 – 30 (single conductor/multiple conductor)
Connection length max.
100 m
Operating temperature
-10 – 55 °C
Ambient temperature max.
55 °C (UL)
Storage temperature
-20 – 85 °C
Relative humidity
10 % – 95 %
Max. altitude (above sea level)
2000 m above sea level
¨
T
Input_filter
= max. filter time related to the settings on the project inputs (see section "INPUTS").