Operating Instructions
Modular Safety Control System MSC
54
(Translation of the original operating instructions) 2121331-04-04/19
8.4.2. Module FI8FO2
MEANING
LED
RECTIFICA
TION MEASURE
RUN GREEN
IN F
AIL
RED
EXT F
AIL
RED
SEL
ORANGE
IN1–8 YELLOW
OSSD1/2
RED/GREEN
CLEAR1/2 YELLOW
ST
ATUS1/2 YELLOW
Internal err
or
OFF
Flashes 2 or 3
times
OFF
Indicates the physical
addr
ess of the module
OFF
Red
OFF
OFF
Ì
Send module to EUCHNER for r
epair
Compatibility err
or
OFF
Flashes 5
times
OFF
Flashes 5
times
Flashes 5 times
Flashes 5
times
Flashes 5
times
Ì
Firmwar
e version not com
-
patible with MSC-CB. Send to EUCHNER for firmwar
e
upgrade.
OSSD output err
or
OFF
Flashes 4
times
OFF
OFF
Flashes 4 times (only the LED corr
esponding
to the output in the err
or mode)
OFF
OFF
Ì
Check OSSD1/2 connections
Ì
If the pr
oblem persists, send
FI8FO2 to EUCHNER for repair
.
Err
or during communi
-
cation with base unit
OFF
Flashes 5
times
OFF
OFF
OFF
OFF
OFF
Ì
Restar
t system.
Ì
If the pr
oblem persists, send
FI8FO2 to EUCHNER for repair
.
Err
or in another
extension module or MSC-CB
OFF
ON
OFF
OFF
OFF
OFF
OFF
Ì
Restar
t system.
Ì
Check which module is in the ERROR mode.
Extension module of the same type with the same addr
ess
detected
OFF
Flashes 5
times
Flashes 5
times
OFF
OFF
OFF
OFF
Ì
Change addr
ess of the mod
-
ule (see section NODE_SEL)
Internal node detection err
or
OFF
Flashes 3
times
OFF
RECTIFICA
TION
MEASURE
OFF
OFF
OFF
OFF
Ì
Send to EUCHNER for r
epair
.
Table 47:
Tr
oubleshooting FI8FO2
Figur
e 28:
FI8FO2