109
2121331-04-04/19 (Translation of the original operating instructions)
Operating Instructions
Modular Safety Control System MSC
EN
Output Test: Using this option you can select which test output signals are to be sent to the pressure sensitive mat contacts.
Short circuits between the wires can be detected and rectified by means of this check. For this purpose it is necessary to
configure the test output signals (from the test output signals available). The test signals are obligatory.
StartUp Test: If selected, the test is undertaken on switching on the external components. This test is undertaken by standing
on and clearing the pressure sensitive mat to carry out one complete function test and to activate the output. This test is
only requested on starting the machine (on switching on the module).
Filter (ms): This parameter makes it possible to filter the signals that are received from the external contactors. This filter
can be set to between 3 and 250 ms and removes any contact bounce. The time set for the filter affects the calculation of
the total response time of the module.
Enable Error Out: If selected, an error detected by the function block is displayed.
Item Description: Here you can enter a functional description for the component. This text is displayed in the upper part of
the symbol.