Modular Safety Control System MSC
EN
8.4.3. Module FI8
MEANING
LED
RECTIFICA
TION MEASURE
RUN GREEN
IN F
AIL
RED
EXT F
AIL
RED
SEL
ORANGE
IN1–8 YELLOW
Internal err
or
OFF
Flashes 2 or 3 times
OFF
Indicates the physical addr
ess of the module
OFF
Ì
Send module to EUCHNER for r
epair
.
Compatibility err
or
OFF
Flashes 5 times
OFF
Flashes 5 times
Ì
Firmwar
e version not compatible with
MSC-CB. Send to EUCHNER for firmwar
e
upgrade.
OSSD output err
or
OFF
Flashes 4 times
OFF
OFF
Ì
Restar
t system.
Ì
If the pr
oblem persists, send FI8 to
EUCHNER for r
epair
.
Err
or during communi
-
cation with base unit
OFF
Flashes 5 times
OFF
OFF
Ì
Restar
t system.
Ì
If the pr
oblem persists, send FI8 to
EUCHNER for r
epair
.
Err
or in another exten
-
sion module or MSC-CB
OFF
ON
OFF
OFF
Ì
Restar
t system.
Ì
Check which module is in the ERROR mode.
Extension module of the same type with the same addr
ess detected
OFF
Flashes 5 times
Flashes 5 times
OFF
Ì
Change addr
ess of the module (see
section NODE_SEL)
Internal node detection err
or
OFF
Flashes 3 times
OFF
Flashes 3 times
OFF
Ì
Send to EUCHNER for r
epair
.
Table 48:
Tr
oubleshooting FI8
Figur
e 29:
FI8