9.2.2.8. Operating mode selection (MOD-SEL)
Using the MOD-SEL function block the input status of an operating mode selector switch (up to 4 inputs) is checked. If only
one of the IN inputs is "1" (TRUE), the corresponding OUTPUT output is also "1" (TRUE). In other cases, i.e. if all IN inputs
are "0" (FALSE) or more than one IN input is "1" (TRUE), all OUTPUT outputs are "0" (FALSE).
Figure 99: MOD-SEL
Parameter
Input Type:
Ì
Double Switch – makes it possible to connect operating mode selector switches with two switch positions.
Ì
Triple Switch – makes it possible to connect operating mode selector switches with three switch positions.
Ì
Quadruple Switch – makes it possible to connect operating mode selector switches with four switch positions.
Filter (ms): Makes it possible to filter the signals that are received from the operating mode selector switch. This filter can
be set to between 3 and 250 ms and removes any contact bounce. The time set for the filter affects the calculation of the
total response time of the module.
Simultaneity (ms): Is always selected. Defines the maximum permissible time (ms) between the switching of the different
signals received from the external contacts on the device.
Enable Error Out: If selected, an error detected by the function block is displayed.
Item Description: Here you can enter a functional description for the component. This text is displayed in the upper part of
the symbol.