Low AC Alarm
(10.107) is displayed from step 2 on the figure above.
The functionality described for
Low DC Link Operation
(06.077) is supported across Frames 02-09. For Frames 05 and above, the minimum supply voltage supported is 330V DC (233VAC
RMS)
Parameter
06.084
UTC Offset
Short description
UTC Offset
Mode
Open
‑
loop
Minimum
-24.00
Maximum
24.00
Default
0.00
Units
Hours
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW
UTC Offset
(06.084) is an offset, specified in hours, applied to the selected clock source (see
Date/Time Selector
(06.019)). This could be used for time zone offsets etc. The offset will be
applied to the time obtained from the selected clock source, in addition to any offset already applied to the time from that source.
Parameter
06.089
DC Injection Active
Short description
Indicates when d.c. injection is active.
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit User Save
Update Rate
4ms
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
This flag is high when the sequencer is in the dc injection state and low for all other conditions.
98
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...