Binary sum
The binary sum function is always active even if the destination is not routed to valid a parameter. The update rate for the binary sum is always 4ms.
The output of the binary sum block is given by
Binary Sum Output
(09.032) =
Binary Sum Offset
(09.034) + (
Binary Sum Ones
(09.029) x 1) + (
Binary Sum Twos
(09.030) x 2) + (
Binary Sum Fours
(09.031) x 4)
Binary Sum Destination
(09.033) defines the destination for the binary sum output. The routing for this destination is special if the maximum of the
destination parameter ≤ 7 + [
Binary Sum Offset
(09.034)] as follows:
Destination parameter =
Binary Sum Output
(09.032), subject to the parameter minimum
Otherwise
Binary Sum Output
(09.032) is routed in the same way as any other destination where the destination target is at its full scale value when the
Binary Sum Output
(09.032) = 7 + Offset.