![Emerson unidrive m200 Parameter Reference Manual Download Page 42](http://html.mh-extra.com/html/emerson/unidrive-m200/unidrive-m200_parameter-reference-manual_102553042.webp)
Parameter
02.041
S Ramp Set-up Mode
Short description
Defines the mode used by the S ramp system
Mode
Open
‑
loop
Minimum
0
Maximum
2
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
S Ramp Set-up Mode
(02.041) defines the method used to set up the S ramp function.
0: Single maximum rate of change of acceleration
The maximum rate of change of acceleration in either direction, when the frequency is changing away from or towards zero, is defined by
Max Rate Of Change Of Acceleration
(02.007).
1: S ramp percentage
A single maximum rate of change of acceleration is used in either direction, when the frequency is changing away from or towards zero, but this is
specified as the percentage of the ramp from zero to Maximum frequency which is covered by the S shaped profile. See
S Ramp Percentage
(02.040).
2: Four independent maximum rate of change of acceleration values
The maximum rate of change of acceleration can be specified as four independent values. See
Max Rate Of Change Of Acceleration
(02.007).
Parameter
02.042
Maximum Rate Of Change Of Acceleration 1
Short description
Defines the 1st maximum rate of change of acceleration used by the S ramp system
Mode
Open
‑
loop
Minimum
0.0
Maximum
300.0
Default
0.0
Units
s²/100Hz
Type
32 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
1
Coding
RW
If
S Ramp Set-up Mode
(02.041) = 2 it is possible to set up four independent maximum rate of change of acceleration values as shown in the diagram
below. The values from 1 to 4 correspond to
Maximum Rate Of Change Of Acceleration 1
(02.042) to
Maximum Rate Of Change Of Acceleration 4
(02.045) respectively.
42
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...