![Emerson unidrive m200 Parameter Reference Manual Download Page 253](http://html.mh-extra.com/html/emerson/unidrive-m200/unidrive-m200_parameter-reference-manual_102553253.webp)
81
*Image is not compatible with the control board
serial number
As 80.
Recommended actions:
Contact the supplier of the drive.
Trip
dESt
Value
199
Short description
A parameter is being changed by more than 1 routing destination
This trip indicates that destination output parameters of two or more logic functions within the drive are writing to the same parameter.
Recommended actions:
Set Pr
mm.000
to "Destinations" or 12001 and check all visible parameters in all menus for parameter write conflicts
Trip
Dr.Cf
Value
232
Short description
Incorrect configuration data
The power stage hardware does not match the drive configuration data.
Sub-
trip
Reason
1
The power stage hardware does not match the drive configuration data (size 5
and above).
2
The power stage hardware detected is invalid.
3
The power stage hardware does not match the drive configuration data (Sizes 1 -
4)
Recommended actions:
Return the drive to the supplier.
Trip
EEF
Value
31
Short description
Non-volatile memory failure
This trip indicates that default parameters have been loaded because of one of the reasons given below.
Sub-
trip
Reason
1
The most significant digit of the internal parameter database version number has changed.
2
The CRC’s applied to the parameter data stored in internal non-volatile memory indicate that a valid set of parameters cannot be
loaded.
3
The drive mode restored from internal non-volatile memory is outside the allowed range for the product or the derivative image does
not allow the previous drive mode.
4
The drive derivative image has been changed and it has changed the customisation of the drive core menus.
5
The power stage hardware has been changed and changed the customisation of the drive core menus.
6
Reserved
7
Reserved
8
The control board hardware has been change and changed the customisation of the drive core menus.
9
The checksum on the non-parameter area of the EEPROM has failed.
The drive holds two banks of user save parameters and two banks of power down save parameters in non-volatile memory. If the last bank of either set of parameters that was saved
is corrupted a
User Save
or
Power Down Save
trip is produced. If one of these trips occurs the parameters values that were last saved successfully are used. It can take some time
to save parameters when requested by the user and if the power is removed from the drive during this process it is possible to corrupt the data in the non-volatile memory.
If both banks of user save parameters or both banks of power down save parameters are corrupted or one of the other conditions given in the table above occurs
EEPROM Fail.
xxx
trip is produced. If this trip occurs it is not possible to use the data that has been saved previously, and so the drive will be loaded with default parameters. The trip can only be reset if
Parameter mm.000
(mm.000) is set to 10, 11, 1233 or 1244 or if
Load Defaults
(11.043) is set to a non-zero value.
Trip
Et
Value
6
Short description
External trip generated by the application
External trip is initiated as shown in the table below.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
253
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...