Parameter
07.061
Analog Input 1 Minimum Reference
Short description
Defines the minimum reference for analog input 1
Mode
Open
‑
loop
Minimum
0.00
Maximum
100.00
Default
0.00
Units
%
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW
Analog Input 1
(07.001) can be scaled and limited using the following parameters:
Analog Input 1 Minimum Reference
(07.061)
Analog Input 1 At Minimum Reference
(07.062)
Analog Input 1 Maximum Reference
(07.063)
Analog Input 1 At Maximum Reference
(07.064)
Parameters above can be selected to limit the range of
Analog Input 1
(07.001) and also scale it between the minimum and maximum reference.
If
Analog Input 1 Minimum Reference
(07.061) ≥
Analog Input 1 Maximum Reference
(07.063) then A
i1
= 0.00%whatever the input level.
Input Level is limited between
Analog Input 1 At Minimum Reference
(07.062) and
Analog Input 1 At Maximum Reference
(07.064)
Analog Input 1
(07.001) = [(
Analog Input 1 At Maximum Reference
(07.064) -
Analog Input 1 At Minimum Reference
(07.062)) / (
Analog Input 1 Maximum Reference
(07.063) -
Analog Input 1 Minimum Reference
(07.061))] x (Input level -
Analog Input 1 Minimum Reference
(07.061)) +
Analog Input 1 At Minimum Reference
(07.062).
108
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...