![Emerson unidrive m200 Parameter Reference Manual Download Page 27](http://html.mh-extra.com/html/emerson/unidrive-m200/unidrive-m200_parameter-reference-manual_102553027.webp)
Parameter
01.057
Force Reference Direction
Short description
Defines the direction of the reference
Mode
Open
‑
loop
Minimum
0
Maximum
2
Default
0
Units
Type
8 Bit Volatile
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
None
1
For
2
Rev
If
Force Reference Direction
(01.057) = 0 then it has no effect. If
Force Reference Direction
(01.057) is non-zero then the modulus of the reference is used and
the sign is defined by the value of
Force Reference Direction
(01.057). If
Force Reference Direction
(01.057) = 1 then
Pre-skip Filter Reference
(01.002) is
always positive, and if
Force Reference Direction
(01.057) = 2 then
Pre-skip Filter Reference
(01.002) is always zero or negative.
Parameter
01.069
Reference in rpm
Short description
Displays the value of the reference in rpm
Mode
Open
‑
loop
Minimum
-33000
Maximum
33000
Default
Units
rpm
Type
32 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Reference in rpm
(01.069) =
Pre-ramp Reference
(01.003) x 60 / Pole Pairs (see
Number Of Motor Poles
(05.011)).
Parameter
01.070
Clamped Reference
Short description
Displays the reference that is provided for the PID controller
Mode
Open
‑
loop
Minimum
−VM_SPEED_FREQ_REF
Maximum
VM_SPEED_FREQ_REF
Default
Units
Hz
Type
32 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
2
Coding
RO, VM, ND, NC, PT
The
Clamped Reference
(01.070) is provided as a source for various drive user functions.
Parameter
01.071
Alternative Reference
Short description
Defines the reference which is used as a destination for the output of the PID controller
Mode
Open
‑
loop
Minimum
−VM_SPEED_FREQ_REF
Maximum
VM_SPEED_FREQ_REF
Default
0.00
Units
Hz
Type
32 Bit Volatile
Update Rate
4ms read
Display Format
Standard
Decimal Places
2
Coding
RO, VM, NC
Alternative Reference
(01.071) is provided as a destination for an alternative reference if required (such as a drive user function output).
If
Alternative Reference
(01.071) has been programmed as a destination,
Alternative Reference Enable
(01.072) is set to 1 automatically so that the alternative
reference is selected.
Parameter
01.072
Alternative Reference Enable
Short description
Indicates when the Alternative Reference is being used
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
See
Alternative Reference
(01.071).
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
27
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...