Menu 3 −
Frequency Monitoring and Speed Feedback
Mode: Open
‑
loop
The drive controls asynchronous machines in open loop control with respect to frequency and current. The open loop asynchronous control is further broken down into vector and fixed boost modes.
Parameter
03.001
Final Demand Reference
Short description
Displays the final reference to the frequency controller
Mode
Open
‑
loop
Minimum
−VM_FREQ
Maximum
VM_FREQ
Default
Units
Hz
Type
32 Bit Volatile
Update Rate
16ms
Display Format
Standard
Decimal Places
2
Coding
RO, FI, VM, ND, NC, PT
Final Demand Reference
(03.001) shows the fundamental drive frequency demand from the
Post Ramp Reference
(02.001) and the
Hard Frequency Reference
(03.022) (if enabled).
Parameter
03.005
Zero Frequency Threshold
Short description
Defines the threshold for detecting the zero frequency condition
Mode
Open
‑
loop
Minimum
0.00
Maximum
20.00
Default
2.00
Units
Hz
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
2
Coding
RW, BU
If the
Post Ramp Reference
(02.001) is at or below the level defined by this parameter in either direction
Zero Frequency
(10.003) = 1, otherwise
Zero Frequency
(10.003) = 0.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
45
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...