Parameter
05.088
Ur Mode Pre-Flux delay
Short description
The delay begins as the motor starts to run and during the pre-flux delay the torque axis voltage
compensation is held at zero.
Mode
Open
‑
loop
Minimum
0.0
Maximum
0.7
Default
0.1
Units
s
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
1
Coding
RW
Setting
Ur Mode Pre-Flux delay
to a value from 0.0s to 0.7s will configure the Ur mode pre-flux delay. The delay begins as the motor starts to run and during
the pre-flux delay the torque axis voltage compensation is held at zero. The delay provides time for the flux to build up to reduce the risk of unstable
behaviour during motor starting. The user configurable delay function has been added for use with the brake macro, where the mechanical brake is holding
the shaft while the motor is started. The delay can be set depending on the motor and the system.
78
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...