Parameter
04.025
Low Frequency Thermal Protection Mode
Short description
Set to enable low frequency thermal protection mode
Mode
Open
‑
loop
Minimum
0
Maximum
1
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Motor Thermal Time Constant 1
(04.015).
Parameter
04.026
Percentage Torque
Short description
Displays the torque producing current as a percentage or motor rated current
Mode
Open
‑
loop
Minimum
−VM_USER_CURRENT
Maximum
VM_USER_CURRENT
Default
Units
%
Type
16 Bit Volatile
Update Rate
Background read
Display Format
Standard
Decimal Places
1
Coding
RO, FI, VM, ND, NC, PT
Percentage Torque
(04.026) gives the
Torque Producing Current
(04.002) as a percentage of the rated torque producing current for the motor, but with
an additional adjustment above rated frequency so that it gives percentage torque. Below rated frequency,
Percentage Torque
(04.026)
=
Percentage Load
(04.020). Above rated frequency, the
Percentage Torque
(04.026) is adjusted as follows:
Percentage Torque
(04.026) =
Percentage Load
(04.020) x
Motor Rated Frequency
(05.006) /
Output Frequency
(05.001)
Parameter
04.036
Motor Protection Accumulator Power-up Value
Short description
Defines the initial power-up value of the motor protection accumulator
Mode
Open
‑
loop
Minimum
0
Maximum
2
Default
0
Units
Type
8 Bit User Save
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
Pr.dn
1
0
2
Real t
See
Motor Thermal Time Constant 1
(04.015).
Parameter
04.041
User Over Current Trip Level
Short description
Defines the trip level for the user over-current trip as a percentage of the drive over current trip level.
Mode
Open
‑
loop
Minimum
0
Maximum
100
Default
100
Units
%
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, RA
The User Over-Current Trip protection level in % of
Full Scale Current Kc
(11.061) which is the full scale current in r.m.s. Amps. The User Over-Current
Trip may be used to limit the output current of the drive when supplying a motor with a lower current rating than the drive. If the value
of
User Over Current Trip Level
(04.041) is set at 100%, the user over-current trip is disabled.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
61
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...