![Emerson unidrive m200 Parameter Reference Manual Download Page 267](http://html.mh-extra.com/html/emerson/unidrive-m200/unidrive-m200_parameter-reference-manual_102553267.webp)
Sub-trip
Reason
1
No module was fitted previously
2
A module with the same identifier is fitted, but the set-up menu has been changed, and so default
parameters have been loaded for this menu.
3
A module with the same identifier is fitted, but the applications menu for this option has been
changed, and so default parameters have been loaded for this menu.
4
A module with the same identifier is fitted, but the set-up and applications menu have been
changed, and so default parameters have been loaded for these menus.
>99
Shows the identifier of the module previously fitted.
Recommended actions:
Turn off the power, ensure the correct option module is installed and re-apply the power.
Confirm that the currently installed option module is correct, ensure option module parameters are set correctly and perform a user save in Pr
mm.000
.
Trip
SL.Er
Value
202
Short description
Error generated by the option module
The option module in option slot 1 has indicated an error. The option module can give the reason for the error and this is shown in the sub-trip number. As default the sub-trip number
is shown as a number on the display, however, it is possible for the option module to supply sub-trip number strings which will be displayed instead of the number if available.
Recommended actions:
See relevant
Option Module User Guide
for details of the trip.
Trip
SL.HF
Value
200
Short description
Error in communication with an option module
This trip indicates that there is a fault with the option module in option slot 1 that means that this module cannot operate. The possible causes of the trip are given by the sub-trip
value.
Sub-trip
Reason
1
The module category cannot be identified
2
All the required customisable menu table information has not been supplied or the tables supplied
are corrupt
3
There is insufficient memory available to allocate the comms buffers for this module.
4
The module has not indicated that it is running correctly during drive power-up
5
The module has been removed after power-up or it has ceased to indicate to the drive processor
that it is still active.
6
The module has not indicated that it has stopped accessing drive parameters during a drive mode
change
7
The module has failed to acknowledge that a request has been made to reset the drive processor.
8
The drive failed to read the menu table from the module correctly during drive power-up.
9
The drive failed to upload menu tables from the module and timed-out (5s).
10
Menu table CRC invalid.
Recommended actions:
Ensure the option module is installed correctly.
Replace the option module.
Replace the drive.
Trip
SL.nF
Value
203
Short description
Option module no longer fitted
Any option module fitted in the drive is identified at power-up and the option fitted is stored by the drive in its non-volatile memory. If an option module was fitted in slot 1 at power-
down, but that option module has subsequently been removed before power up then this trip is produced. The sub-trip number gives the identification code of the option module that
has been removed. Drive user parameters must be saved to prevent this trip on the next power-up.
Recommended actions:
Ensure the option module is installed correctly.
Re-install the option module.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
267
Summary of Contents for unidrive m200
Page 1: ...Parameter Reference Guide Unidrive M200 Open loop Mode Issue 01 05 00 10 ...
Page 30: ...30 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...
Page 83: ...Enable logic Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 83 ...
Page 125: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 125 ...
Page 145: ...Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 145 ...
Page 204: ...204 Unidrive M200 Parameter Reference Guide Issue 01 05 00 10 ...