Maintenance and Troubleshooting
November 2010
227
Table 7-2. Instrument Troubleshooting (Continued)
Symptom
Action
Possible Cause
6. Block dynamic parameters do not
update
6.a Block actual mode is Out of Service
6.a Change the block target mode to an operational
mode (see F
OUNDATION
fieldbus Communication,
Appendix D and host system documentation).
7. Transducer block Setpoint
(FINAL_VALUE [13]) is not being
automatically updated from the AO
block.
7.a Transducer block mode in not Auto.
7.a Change transducer block mode to Auto.
7.b Change Outblock Selection to AO Control.
8. Transducer block setpoint
Setpoint(D) (SETPOINT_D [32]) is not
being automatically updated from the
DO block.
8.a Transducer block mode is not Auto.
8.a Change transducer block mode to Auto.
8.b Change Outblock Selection to DO Control.
9. Valve does not move when the set
point is changed
9.a A function block actual mode is Out of Service or
Transducer Block Actual mode is Out of Service or
Manual.
9.a1 Change the target mode to an operational mode
(see F
OUNDATION
fieldbus Communication,
Appendix D and host system documentation).
9.a2 Verify that the correct block (AO or DO) is
configured in Feature Select in the resource block.
Only the selected out block is able to set the
transducer setpoint and move the valve.
9.b Pneumatic connections are incorrect or supply
pressure is incorrect
9.b Check pneumatic connections and supply
pressure. Be sure supply pressure regulator is set
correctly (see Pneumatic Connections on page 16 of
the Installation Section).
9.c Instrument is in fault state.
9.c Set Clear FState to Clear (Refer to Fault State on
page 33 of the Detailed Setup / Blocks Section, or
host system documentation).
9.d Apply a pneumatic pressure to the valve actuator
and check valve action.
9.e The I/P converter or relay has failed.
9.e Replace the I/P converter or relay (see Replacing
the I/P Converter on page 222).
10. Valve does not stroke from 0 to
100% with set point change
10.a Insufficient supply pressure or leak in pneumatic
connections.
10.a Check supply pressure and supply pressure
regulator setting. Check for leaks around pneumatic
connections.
10.b Check the AO Block values of SP_HI_LIMIT
and SP_LO_LIMIT (see page 106 of the Detailed
Setup / Blocks Section or host system
documentation).
11. Deviation between set point and
actual valve position remains.
11.a Digital valve controller output is in cutoff.
11.a Check values for Travel Cutoff High and Travel
Cutoff Low (see page 54 of the Detailed Setup /
Blocks Section or host system documentation).
11.b Digital valve controller is not calibrated correctly
11.b Perform Auto or Manual Travel Calibration
(Travel Calibration on page 200.)
11.c Incorrect turning. Tuning that is too conservative
will result in excess error.
11.c Perform Stabilizing/Optimize Valve Response
procedure to adjust tuning and stabilize/optimize
valve response (see Stabilize/Optimize on page 52).
12. The valve cycles, does not stay on
set point.
12.a Large amount of packing friction.
12.a1 Perform Stabilizing/Optimize Valve Response
procedure to adjust tuning and stabilize/optimize
valve response (see Stabilize/Optimize on page 52).
12.a2 Use a larger size actuator.
13. Valve responds too slowly.
13.a Insufficient instrument gain.
13.a Perform Stabilize/Optimize Valve Response
procedure to adjust tuning and stabilize valve
response (see Stabilize/Optimize on page 52).
13.b I/P converter input filter clogged or air blockage in
I/P ass’y nozzle block.
13.b1 Replace I/P converter filter (see Replacing the
I/P Filter on page 221).
13.b2 Replace I/P converter (see Replacing the I/P
Converter on page 222).
13.c O-ring(s) between I/P converter missing or hard
and flattened losing seal.
13.c Replace O-ring(s) (refer to the I/P Converter
section on page 221).
−
Continued
−
7
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...