DVC6200f Digital Valve Controller
November 2010
138
ISEL Function Block Parameter List
Read/Write Capability: RO
−
Read Only, RW
−
Read Write
Mode: The block mode(s) required to write to the parameter
Double indentations and shaded Index Numbers indicate sub-parameters
Table 4-40. Input Selector Function Block Parameter Definitions
Label
PARAMETER_NAME
Index
Number
RO /
RW
Block
Mode
Range
Initial
Value
Description
Static Revision
ST_REV
1
RO
N/A
0 to 65535
0
Data Type: Unsigned16
The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static parameter value in the
block is changed.
Tag Description
TAG_DESC
2
RW
ALL
7 bit ASCII
spaces
Data Type: Octet String
The user description of the intended application of the
block.
Strategy
STRATEGY
3
RW
ALL
0 to 65535
0
Data Type: Unsigned16
The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.
Alert Key
ALERT_KEY
4
RW
ALL
1 to 255
0
Data Type: Unsigned8
The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.
Block Mode
MODE_BLK
5
Data Type: DS-69
Valid Bits: 7: OOS, 4: MAN,
3: AUTO
The actual, target, permitted, and normal modes of
the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
TARGET
5.1
RW
ALL
OOS, MAN, AUTO
OOS until
block is
configured,
then last
valid target
ACTUAL
5.2
RO
ALL
PERMITTED
5.3
RW
ALL
OOS+MAN+AUTO
OOS+MAN
+AUTO
NORMAL
5.4
RW
ALL
AUTO
Block Error
BLOCK_ERR
6
RO
N/A
1: Block
Configuration Error
7: Input Failure / Bad
PV status
8: Output Failure
14: Power Up
15: Out-of-Service
Dynamic
Data Type: Bit String
0=Inactive
1=Active
This parameter reflects the error status associated
with the hardware or software components
associated with a block. It is a bit string, so that
multiple errors may be shown.
Output
OUT
7
MAN
OOS
Status
OUT_RANGE
Dynamic
Data Type: DS-65
The block output value and status.
Value
Output Range
OUT_RANGE
8
ALL
EU at 100%
EU at 0%
Units Index
Decimal Point
100
0
%
2
Data Type: DS-67
High and low scale values, engineering units code,
and number of digits to the right of the decimal point
associated with OUT.
Grant Deny
GRANT_DENY
9
Data Type: DS-70
Options for controlling access of host computers and
local control panels to operating, tuning, and alarm
parameters of the block. Not used by device.
GRANT: 0=N/A, 1=granted
DENY: 0=N/A, 1=denied
GRANT
9.1
ALL
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
DENY
9.2
ALL
All bits:0
Status Options
STATUS_OPTS
10
OOS
2: Use Uncertain as
GOOD
8: Uncertain if MAN
All bits: 0
Data Type: Bit String
Allows you to select options for status handling and
processing. The supported status option for the input
selector block is: “Use Uncertain as Good”,
“Uncertain if Man mode.”
Input 1
IN_1
11
ALL
Status
BAD
NC
constant
Data Type: DS-65
The block input value and status.
Value
0
−
Continued
−
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...