DO Function Block
November 2010
183
DO Function Block Parameter List
Read/Write Capability: RO
−
Read Only, RW
−
Read Write
Mode: The block mode(s) required to write to the parameter
Double indentation and shaded Index Number indicates sub-parameter
Table 4-72. Discrete Output Function Block Parameter Definitions
Label
PARAMETER_NAME
Index
Number
RO /
RW
Mode
Range
Initial Value
Description
Static Revision
ST_REV
1
RO
N/A
0 to 65535
0
Data Type: Unsigned16
The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static parameter value in
the block is changed.
Tag Description
TAG_DESC
2
RW
ALL
7 bit ASCII
Spaces
Data Type: Octet String
The user description of the intended application of
the block.
Strategy
STRATEGY
3
RW
ALL
0 to 65535
0
Data Type: Unsigned16
The strategy field can be used to identify grouping
of blocks. This data is not checked or processed
by the block.
Alert Key
ALERT_KEY
4
RW
ALL
1 to 255
0
Data Type: Unsigned8
The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.
Block Mode
MODE_BLK
5
Data Type: DS-69
Valid Bits: 7: OOS, 5: LO, 4: MAN, 3: AUTO
2: CAS, 1: RCAS
The actual, target, permitted, and normal modes of
the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
TARGET
5.1
RW
ALL
OOS
MAN
AUTO
AUTO-CAS,
AUTO-RCAS
OOS until
block is
configured,
then last valid
target
ACTUAL
5.2
RO
ALL
OOS
PERMITTED
5.3
RW
ALL
OOS+MAN+AUTO+
CAS+RCAS
OOS+MAN+
AUTO+CAS
+RCAS
NORMAL
5.4
RW
ALL
AUTO+CAS
Block Error
BLOCK_ERR
6
RO
N/A
1: Block Configuration
Error
3: Simulate Active
4: Local Override
5: Device Fault State
Set
7: Input Failure / Bad
PV Status
8: Output Failure
14: Power-up
15: Out-of-Service
Dynamic
Data Type: Bit String
0=Inactive
1=Active
This parameter reflects the error status associated
with the hardware or software components
associated with a block. It is a bit string, so that
multiple errors may be shown.
Process Value Discrete
PV_D
7
RO
N/A
PV_D Status set equal
to Readback_D Status
Dynamic
Data Type: DS-66
The discrete process variable calculated from
READBACK_D.
Setpoint Discrete
SP_D
8
OOS
MAN
AUTO
PV_STATE
Data Type: DS-66
The discrete target block output value (set point).
Output Discrete
OUT_D
9
MAN
OUT_STATE
Data Type: DS-66
Position target of valve. 0=closed, 1=open, 2
−
100
position the value in 5% steps.
Simulate Discrete
SIMULATE_D
10
Data Type: DS-83
Allows the transducer discrete input or output to
the block to be manually supplied when simulate is
enabled. When simulation is disabled, the simulate
value and status track the actual value and status.
SIMULATE_STATUS
10.1
ALL
0
SIMULATE_VALUE
10.2
ALL
0
TRANSDUCER_STATUS
10.3
RO
0
TRANSDUCER_VALUE
10.4
RO
0
ENABLE/DISABLE
10.5
ALL
0=Not initialized
1=Simulation Disabled
2=Simulation Active
1
−
Continued
−
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...