DI Function Block
November 2010
195
Table 4-81. Discrete Input Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial Value
Range
Block
Mode
RO /
RW
Index
Number
Transducer State
XD_STATE
10
ALL
0
Data Type: Uint16
Index to the text describing the states of a
discrete for the value obtained from the
transducer.
Output State
OUT_STATE
11
ALL
0
Data Type: Unsigned16
Index to the text describing the states of a
discrete output.
Grant Deny
GRANT_DENY
12
Data Type: DS-70
Options for controlling access of host
computers and local control panels to
operating, tuning, and alarm parameters of
the block.
GRANT: 0=NA, 1=granted
DENY: 0=NA, 1=denied
GRANT
12.1
ALL
0: Program
1: Tune
2: Alarm
3: Local
All bits:0
DENY
12.2
ALL
All bits: 0
I/O Options
IO_OPTS
13
OOS
0: Invert
All bits:0
Data Type: Bit String
0=Disable
1=Enable
Allows you to select how the I/O signals are
processed.
Status Options
STATUS_OPTS
14
OOS
3=Propagate Failure
Forward
8=Uncertain in MAN mode
All bits:0
Data Type: Bit String
0=Disable
1=Enable
Options the user may select for the block
processing of status.
DI Channel
CHANNEL
15
OOS
0=undefined
23=Valve Position or
Pressure (Discrete)
24= PV > 97%
25= PV < 3%
26=PV Below LO LO limit
27=PV Below LO limit
28=PV Above HI limit
29=PV Above HI HI limit
30=PV Within Proximity of
LO LO
31=PV Within Proximity of
LO
32=PV within Proximity of
HI
33=PV within Proximity of
HI HI
0=Undefined
Data Type: Unsigned16
Defines the functionality of the discrete input.
See I/O Selection for details. Refer to table
4-77.
Process Value Filter Time
PV_FTIME
16
ALL
Positive
0
Data Type: Float
Time that FIELD_VAL_D must be in a new
state, before the change is reflected to PV_D
and OUT_D.
Field Value Discrete
FIELD_VAL_D
17
RO
0
Data Type: DS-66
Raw value of the field device discrete input,
with a status reflecting the transducer
condition.
Update Event
UPDATE_EVT
18
Data Type: DS-73
This alert is generated by any change to the
static data.
UNACKNOWLEDGED
18.1
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
UPDATE_STATE
18.2
RO
N/A
0=Undefined
1=Update Reported
2=Updated not reported
0=Undefined
TIME_STAMP
18.3
RO
N/A
0
STATIC_REVISION
18.4
RO
N/A
0
RELATIVE_INDEX
18.5
RO
N/A
0
−
Continued
−
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...