Transducer Block
November 2010
55
pressure that corresponds to 0% valve travel when
Zero Power Condition is closed, or 100% valve travel
when Zero Power Condition is open. The pressure
must be less than the Pressure Range Hi.
Input Characterization
Field Communicator
TB
>
Configure/Setup
>
Detailed Setup
>
Response Control
>
Input Characterization
Input Characterization (INPUT_CHAR [50]) defines
the relationship between the travel target and the
setpoint received from the output block. Travel target
is the output from the characterization function.
Custom Characterization Table
Field Communicator
TB
>
Configure/Setup
>
Detailed Setup
>
Response Control
>
Custom Characterization
Table
You can select from the three fixed input
characteristics shown in figure 4-1 or you can select a
custom characteristic. Figure 4-1 shows the
relationship between the travel target and travel set
point for the fixed input characteristics.
You can specify 21 points on a custom characteristic
curve. Each point defines a travel target, in % of
ranged travel, for a corresponding set point, in % of
ranged set point. Set point values range from
−
25.0%
to 125%. Before modification, the custom
characteristic is linear. You cannot modify the custom
points if the Input Characterization (INPUT_CHAR
[50]) is set to custom.
Outblock Selection
Field Communicator
TB
>
Configure/Setup
>
Detailed Setup
>
Response Control
>
Outblock Selection
Outblock Selection (OUTBLOCK_SEL [96]) defines
which output function block will control the setpoint of
the valve. The output block that is not selected will
shed its mode to reflect that it does not have control of
the valve.
Alerts
The DVC6200f provides two levels of alerts;
Instrument alerts and PlantWeb alerts.
Instrument Alert Conditions
Instrument Alert Conditions, when enabled, detect
many operational and performance issues that may be
of interest. To view these alerts, the user must open
the appropriate status screen on a host such as
DeltaV, ValveLink software or a Field Communicator.
T
ravel T
arget,
%
Set Point, %
−
25
0
125
100
−
25
0
125
100
−
25
0
125
100
Input Characteristic Linear
Input Characteristic Equal Percentage
Input Characteristic Quick Opening
100
0
−
25
125
T
ravel T
arget,
%
100
0
−
25
125
T
ravel T
arget,
%
100
0
−
25
125
A6535-1/IL
Set Point, %
Set Point, %
Figure 4-1. Travel Target Versus Ranged Set Point, for Various
Input Characteristics (Zero Power Condition = Closed)
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...