DVC6200f Digital Valve Controller
November 2010
70
these alerts for testing. In order to enable PWA
Simulate, the Aux Terminal must be jumpered.
PlantWeb Alert Simulate is cleared on a power cycle.
It can also be cleared manually, or by removing the
Aux terminal jumper.
Simulate Active Alerts
Failed Active
Permits simulating an active Failed alarm
(FAILED_ACTIVE [59]).
Maintenance Active
Permits simulating an active Maintenance alarm
(MAINT_ACTIVE [60]).
Advise Active
Permits simulating an active Advisory alarm
(ADVISE_ACTIVE [61]).
PlantWeb Alert Handling
PlantWeb Alerts Set PV Status
When selected, PlantWeb alerts will set the PV status
according to table 4-11.
Block Error Reporting
When enabled, the AO or DO BLOCK_ERR [6]
parameter will report PlantWeb Alerts. the same as
Block Error in the resource block.
Block Error bit 6 (Device Needs Maintenance Soon)
will report any active PlantWeb Maintenance Alert.
Block Error bit 13 (Device Needs Maintenance Now)
will report any active PlantWeb Failed Alert.
Block Errors
Table 4-13 lists conditions reported in the
BLOCK_ERR [6] and XD_ERR [11] parameters.
Conditions in italics are not applicable for the
transducer block and are provided only for your
reference.
Table 4-13. Transducer Block BLOCK_ERR and
XD_ERROR Conditions
Condition
Number
Condition Name and Description
0
Other - (N/A)
1
Block Configuration Error - Indicates that one of the
following parameters have been configured out of the
proper range: 15, 16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
2
Link Configuration Error - (N/A)
3
Simulate Active - Indicates that the simulation jumper is
in place on the aux terminals. This is not an indication
that the I/O blocks are using simulation data. See AO
block parameter SIMULATE [10] and DO block parameter
SIMULATE_D [10].
4
Local Override - (N/A)
5
Device Fault State
−
(NA)
6
Maintenance Needed Soon - (N/A)
7
Input failure/process variable has Bad status - (N/A)
8
Output failure - (N/A)
9
Memory failure - (N/A)
10
Lost Static Data - Indicates that manufacturing functional
or thermal tests were incomplete
11
Lost NV Data - (N/A)
12
Readback Check Failed - (N/A)
13
Device Needs Maintenance Now - Indicates that
manufacturing functional or thermal tests were incomplete
14
Power Up - (N/A)
15
Out of Service - Indicates Out of Service Mode.
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...