Transducer Block
November 2010
91
Table 4-14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial Value
Range
Mode
RO /
RW
Index
Number
SPEC_SHEET_ACT
85
Actuator Size
ACTUATOR SIZE
85.1
RW
ALL
NULL
ALL
Data Type: Visible String
Effective Area
EFFECTIVE AREA
85.2
RW
ALL
0.00
ALL
Data Type: Float
Air
AIR
85.3
RW
ALL
1=open
2=close
0
ALL
Data Type: Enum (Uint8)
Lower Bench Set
LOWER_BENCH_SET
85.4
RW
ALL
0.00
ALL
Data Type: Float
Upper Bench Set
UPPER_BENCH_SET
85.5
RW
ALL
0.00
ALL
Data Type: Float
Nominal Supply Pressure
NOMINAL_SUPPLY_PRESSURE
85.6
RW
ALL
0.00
ALL
Data Type: Float
Spring Rate
SPRING_RATE
85.7
RW
ALL
0.00
ALL
Data Type: Float
Stroking Time Open
STROKING_TIME_OPEN
85.8
RW
ALL
0.00
ALL
Data Type: Float
Seconds
Stroking Time Close
STROKING_TIME_CLOSE
85.9
RW
ALL
0.00
ALL
Data Type: Float
Seconds
Lever Style
LEVER_STYLE
85.10
RW
ALL
1=Pivot Point
2=Rack & Pinion
0
ALL
Data Type: Enum (Uint8)
Lever Arm Length
MOMENT_ARM
85.11
RW
ALL
0.00
ALL
Data Type: Float
DEVICE_RECORD
86
These parameters can only reset
through VL/DD.
Temperature Maximum
TEMP_MAX
86.1
RO
N/A
−
9999.99
N/A
Data Type: Float
Highest temperature recorded
Temperature Maximum Time
TEMP_MAX_TIME
86.2
RO
N/A
Zero time
N/A
Data Type: Time Value
Temperature Minimum
TEMP_MIN
86.3
RO
N/A
9999.99
N/A
Data Type: Float
Lowest temperature recorded
Temperature Minimum Time
TEMP_MIN_TIME
86.4
RO
N/A
Zero time
N/A
Data Type: Time Value
Supply Pressure Maximum
SUPP_PRESS_MAX
86.5
RO
N/A
0.0
N/A
Data Type: Float
Highest supply pressure recorded
Supply Pressure Maximum Time
SUPP_PRESS_MAX_TIME
86.6
RO
N/A
Zero time
N/A
Data Type: Time Value
Supply Pressure Minimum
SUPP_PRESS_MIN
86.7
RO
N/A
9999.99
N/A
Data Type: Float
Lowest supply pressure recorded
Supply Pressure Minimum Time
SUPP_PRESS_MIN_TIME
86.8
RO
N/A
Zero time
N/A
Data Type: Time Value
Comm Error Count
COMM_ERROR_COUNT
86.9
RW
N/A
0
SETUP
Not used by the DVC6200f
Protection
PROTECTION
87
RW
ALL
1=None
2=Calibration
3=Setup & Calibration
4=All
2=Calibration
NONE
Data Type: Enum
Write lock enable/disable. If setting
is at or above a parameters
protection level then that parameter
is read-only.
PERF_DIAG
88
PD Run
PD_COMMAND
88.1
RW
AUTO
MAN
1=PD On
2=PD Off
1=PD On
NONE
Data Type: Enum
Controls whether PD will run or not.
PD Status
PD_STATUS
88.2
RO
ALL
1=Not Running
2=Running
NONE
Data Type: Enum
Status of performance diagnostics.
PD Configuration
PD_CONFIG
88.3
RW
ALL
0
NONE
Data Type: Bit String
Bit string for configuring PD setup
and options.
PD Extra
PD_EXTRA
88.4
RW
ALL
0
NONE
Data Type: Uint32
Extra 32 bit integer for sending
values to PD.
−
Continued
−
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...