ISEL Function Block
November 2010
139
Table 4-40. Input Selector Function Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial
Value
Range
Block
Mode
RO /
RW
Index
Number
Input 2
IN_2
12
ALL
Status
BAD
NC
constant
Data Type: DS-65
The block input value and status.
Value
0
Input 3
IN_3
13
ALL
Status
BAD
NC
constant
Data Type: DS-65
The block input value and status.
Value
0
Input 4
IN_4
14
ALL
Status
BAD
NC
constant
Data Type: DS-65
The block input value and status.
Value
0
Disable Analog Input 1
DISABLE_1
15
ALL
Status
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_1, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Value
0=Use
1=Disable
0
Disable Analog Input 2
DISABLE_2
16
ALL
Status
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_2, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Value
0=Use
1=Disable
0
Disable Analog Input 3
DISABLE_3
17
ALL
Status
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_3, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Value
0=Use
1=Disable
0
Disable Analog Input 4
DISABLE_4
18
ALL
Status
BAD
NC
constant
Data Type: DS-66
Enable/Disable for Input_4, If parameter is TRUE
then input is disabled. If parameter status is BAD it is
not evaluated.
Value
0=Use
1=Disable
0
Select Type
SELECT_TYPE
19
ALL
1=First Good
2=Minimum
3=Maximum
4=Middle
5=Average
6=Hot Spare
0
Data Type: Unsigned8
Determines the selector action
Min Good
MIN_GOOD
20
ALL
1
−
4
0 initial value only
0
Data Type: Unsigned8
The minimum number of inputs which are “good” is
less than the value of MIN_GOOD then set the OUT
status to “bad”.
Selected
SELECTED
21
RO
N/A
Status
Data Type: DS-66
The integer indicating the selected input number.
Value
0
−
8
Dynamic
Operator Select
OP_SELECT
22
ALL
Status
BAD
NC
constant
Data Type: DS-66
An operator settable parameter to force a given input
to be used.
Value
0
−
8
0
−
Continued
−
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...