DVC6200f Digital Valve Controller
November 2010
162
Troubleshooting
Refer to table 4-56 to troubleshoot any problem that
you encounter.
Table 4-56. Troubleshooting
Symptom
Possible Causes
Corrective Action
Mode will not leave OOS
Target mode is not set
Set target mode to something other than OOS
Configuration error
BLOCK_ERR [6] will show the configuration error bit set.
The following are parameters that must be set before the
block is allowed out of OOS:
CHANNEL [15] must be set to a valid value and cannot
be left at initial value of 0.
XD_SCALE [10]. UNITS_INDEX must match the units in
the transducer block channel value.
L_TYPE [16] must be set to Direct, Indirect, or Indirect
Square Root and cannot be left at an initial value of 0.
Resource block
The actual mode of the Resource block is OOS. See
Resource Block Diagnostics for corrective action.
Schedule
Block is not scheduled and therefore cannot execute to go
to Target Mode. Schedule the block to execute.
Process and/or block alarms will not work
Features
FEATURES_SEL [18] in the resource block does not have
Alerts enabled. Enable the Reports Supported bit.
Notification
LIM_NOTIFY [32] in the resource block is not high enough.
Set equal to MAX_NOTIFY [31], also in the resource block.
Status Options
STATUS_OPTS [14] has Propagate Fault Forward bit set.
This should be cleared to cause an alarm to occur.
Value of output does not make sense
Linearization Type
L_TYPE [16] must be set to Direct, Indirect, or Indirect
Square Root and cannot be left at an initial value of 0.
Scaling
Scaling parameters are set incorrectly:
XD_SCALE.EU0 and EU100 should match that of the
transducer block channel value.
OUT_SCALE.EU0 and EU100 are not set properly.
Cannot set HI_LIMIT [28], HI_HI_LIMIT
[26], LO_LIMIT [30], or LO_LO_LIMIT [32]
VALUES
Scaling
Limit values are outside the OUT_SCALE.EU0 and
OUT_SCALE.EU100 values. Change OUT_SCALE [11] or
set values within range.
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...