Transducer Block
November 2010
81
Table 4-14. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial Value
Range
Mode
RO /
RW
Index
Number
Advise Active
ADVISE_ACTIVE
61
RO
(1)
N/A
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
All bits: 0
N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Advise Alert Status
Failed Enable
FAILED_ENABLE
62
RW
ALL
Same as for
FAILED_ACTIVE above
Enabled Bits:
0: Drive Current
2: Processor
Impaired
4: Blocks Set to
Default
5: Travel Sensor
15: Performance
Critical
18: Shutdown
Alert
ALL
Data Type: Bit String (4 byte)
0=disable
1=enable
Failed alert enable. Enable allows
detection of alert. All alerts can be
disabled.
Maintenance Enable
MAINT_ENABLE
63
RW
ALL
Same as for
MAINT_ACTIVE above
Enabled Bits:
1: Drive Signal
3: Output Block
Timeout
6: Outlet Pressure
Sensor
9: Supply
Pressure
11: Travel
Deviation
13: Travel
Accumulator
14: Cycle Counter
16: Performance
Reduced
ALL
Data Type: Bit String (4 byte)
0=disable
1=enable
Maintenance alert enable. Enable
allows detection of alert. All alerts
can be disabled.
Advise Enable
ADVISE_ENABLE
64
RW
ALL
Same as for
ADVISE_ENABLE above
Enabled Bits:
8: Temperature
Sensor
9: Supply
Pressure Sensor
10: Temperature
Limit
12: Travel Limit
ALL
Data Type: Bit String (4 byte)
0=disable
1=enable
Advise alert enable. Enable allows
detection of alert. All alerts can be
disabled.
Failed Suppress
FAILED_MASK
65
RW
ALL
Same as for
FAILED_ACTIVE above
All bits: 0
ALL
Data Type: Bit String (4 byte)
0=disable
1=enable
Failed alert mask. MASK controls
whether an alert is reported. If alert
is enabled the alert condition is
evaluated and the ACTIVE
parameter is updated to reflect if
alert is active or not. If the bit is set
reporting is suppressed. Default is
all bits cleared.
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
−
Continued
−
4
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...