DVC6200f Digital Valve Controller
November 2010
18
24/48 VDC
110/220 VAC, etc.
Port A
FOUNDATION FIELDBUS
H1 SEGMENT
Port B
SUPPLY PRESSURE
MONITORING LINE
CONTROL LINE
DVC6200f DIGITAL VALVE
CONTROLLER WITH RELAY C
SPRING RETURN ACTUATOR
NOTES:
1/4-18 NPT X 3/8 OD TUBING
ELECTRICAL WIRING
Figure 2-7. Pneumatic Hookup for Solenoid Testing (Instrument Level PD only)
Vent
WARNING
Personal injury or property damage
can occur from cover failure due to
overpressure. Ensure that the
housing vent opening is open and
free of debris to prevent pressure
buildup under the cover.
WARNING
This unit vents the supply medium
into the surrounding atmosphere.
When installing this unit in a
non-hazardous (non-classified)
location in a confined area, with
natural gas as the supply medium,
you must remotely vent this unit to a
safe location. Failure to do so could
result in personal injury or property
damage from fire or explosion, and
area re-classification.
When installing this unit in a
hazardous (classified) location remote
venting of the unit may be required,
depending upon the area
classification, and as specified by the
requirements of local, regional, and
federal codes, rules and regulations.
Failure to do so when necessary could
result in personal injury or property
damage from fire or explosion, and
area re-classification.
Vent line piping should comply with
local and regional codes, should be as
short as possible with a minimum
inside diameter of 12.7 mm (1/2-inch),
and few bends to reduce case pressure
buildup.
In addition to remote venting of the
unit, ensure that all caps and covers
are correctly installed. Failure to do so
could result in personal injury or
property damage from fire or
explosion, and area re-classification.
The relay constantly bleeds a small amount of supply
medium into the area under the cover. The vent
opening, located below the wiring terminal box on the
side of the housing, should be left open to prevent
pressure buildup under the cover. If a remote vent is
required, the vent lines must be as short as possible
with a minimum number of bends and elbows.
To connect a remote vent, remove the plastic vent.
The vent connection is 3/8 NPT. At a minimum, 12.7
mm (1/2-inch) tubing should be used when installing a
remote vent to prevent excessive pressure from
building up under the cover.
2
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...