DVC6200f Digital Valve Controller
November 2010
258
Table C-3. Using PlantWeb Alerts (Continued)
PlantWeb Alert
(Group)
(Default Alert Category
Alert Condition
(Default)
What the Alert is
Detecting
Effect on Valve /
Instrument
Recommended
Action
Help
Processor Impaired
(Electronics)
(Maintenance)
Program Memory
(Enabled)
A pending Flash or NVM
failure is present.
If configured for Self Test
Shutdown, then the
transducer Actual mode is
placed Out of Service until the
problem is fixed. Out of
Service results in the
instrument output pressure(s)
and actuator position being at
the Zero Power Condition.
Replace PWB
assembly
An error has been
detected in the printed
wiring board (PWB)
assembly. Replace the
PWB assembly.
Static Memory
(Enabled)
A failure of the FRAM memory
where static parameters are
stored.
Processor
(Enabled)
A failure of the main
Processor.
I/O Processor
(Enabled)
A failure of the I/O Processor.
Output Block Timeout
(Configuration)
(Maintenance
Output Block
Timeout
(Disabled)
If the AO or DO block has not
executed for longer than the
configured timeout, this alert is
detected.
If configured for Self Test
Shutdown, then the
transducer Actual mode is
placed Out of Service until the
problem is fixed. Out of
Service results in the
instrument output pressure(s)
and actuator position being at
the Zero Power Condition.
Check Output
Block
The function block
providing the setpoint
for the valve position
(AO or DO function
block) has not
executed within the
user configured time
limit. If configured for
Self Test Shutdown,
the transducer Actual
mode is set to Out of
Service.
1) Download the
control schedule from
the host configuration
device.
2) Make sure the Time
Out Alert Point is
greater than the block
execution schedule.
This alert should only
be utilized in very
critical loops where
execution time is
critical.
Blocks Set to Default
(Configuration)
(Failed)
Blocks Set to
Default
(Enabled)
If the resource block has
undergone Restart with
Defaults.
The transducer “Actual” mode
is placed Out of Service when
the defaults are applied. Out
of service results in the
actuator being at the Zero
Power Condition.
Download device
configuration
When restoring power
to the device, the
configuration
parameters could not
be recalled from
non-volatile memory.
When the instrument
detects this condition,
the transducer Actual
mode is set to Out of
Service.
To correct this
situation, download the
configuration to the
device and set the
Target Mode of the
Resource block.
Shutdown Alert
(Configuration)
(Failed)
N/A
A user configured Self Test
Shutdown condition has taken
the instrument to OOS.
None
−
Indicates why the
instrument remains OOS.
Same as the
configured Self
Test Shutdown.
The instrument Actual
mode remains OOS
due to a configured
Self Test Shutdown,
where Manual
Recovery was
specified, even though
the condition may
have cleared. Check
Recommended Action
for the indicated
condition.
−
Continued
−
C
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...