Maintenance and Troubleshooting
November 2010
221
GE39341
PINS REMOVED FOR
CONNECTOR KEYING
TERMINAL BOX
CONNECTOR
TRAVEL
SENSOR
CONNECTOR
Figure 7-2. Back View of PWB Assembly Sub-Module
3. Connect the travel sensor connector to the PWB
assembly (key 50). Orientation of the connector is
required.
4. Insert the module base (key 2) into the housing
(key 1).
5. Install three socket head screws (key 38) in the
module base into the housing. If not already installed,
press three retaining rings (key 154) into the module
base. Evenly tighten the screws in a crisscross pattern
to a final torque of 16 N
m (138 lbf
in).
6. Attach the cover (key 43) to the module base
assembly.
Submodule Maintenance
The digital valve controller’s module base contains the
following submodules: I/P converter, PWB assembly,
and pneumatic relay. If problems occur, these
submodules may be removed from the module base
and replaced with new submodules. After replacing a
submodule, the module base may be put back into
service.
CAUTION
Exercise care when performing
maintenance on the module base.
Reinstall the cover to protect the I/P
converter and gauges when servicing
other submodules.
In order to maintain accuracy
specifications, do not strike or drop
the I/P converter during submodule
maintenance.
I/P Converter
Refer to figure 8-2 for key number locations. The I/P
converter (key 41) is located on the front of the
module base.
Note
After I/P converter submodule
replacement, calibrate the digital valve
controller to maintain accuracy
specifications.
Replacing the I/P Filter
A screen in the supply port beneath the I/P converter
serves as a secondary filter for the supply medium. To
replace this filter, perform the following procedure:
1. Remove the I/P converter (key 41) and shroud
(key 169) as described in the Removing the I/P
Converter procedure.
2. Remove the screen (key 231) from the supply port.
3. Install a new screen in the supply port as shown in
figure 7-3.
4. Inspect the O-ring (key 39) in the I/P output port. if
necessary, replace it.
5. Reinstall the I/P converter (key 41) and shroud
(key 169) as described in the Replacing the I/P
Converter procedure.
7
Summary of Contents for FIELDVUE DVC6200f
Page 42: ...DVC6200f Digital Valve Controller November 2010 30 4 ...
Page 60: ...DVC6200f Digital Valve Controller November 2010 48 4 ...
Page 108: ...DVC6200f Digital Valve Controller November 2010 96 4 ...
Page 122: ...DVC6200f Digital Valve Controller November 2010 110 4 ...
Page 188: ...DVC6200f Digital Valve Controller November 2010 176 4 ...
Page 200: ...DVC6200f Digital Valve Controller November 2010 188 4 ...
Page 216: ...DVC6200f Digital Valve Controller November 2010 204 5 ...
Page 250: ...DVC6200f Digital Valve Controller November 2010 238 8 ...
Page 254: ...DVC6200f Digital Valve Controller November 2010 242 A ...
Page 284: ...DVC6200f Digital Valve Controller November 2010 272 D ...
Page 290: ...DVC6200f Digital Valve Controller November 2010 278 E ...
Page 308: ...DVC6200f Digital Valve Controller November 2010 296 F ...
Page 312: ...DVC6200f Digital Valve Controller September 2010 300 Notes G Glossary ...
Page 324: ...DVC6200f Digital Valve Controller November 2010 312 F Index ...