94
certain computer in the VPN, please enter his IP address here. As an option, the input of an additional
IP address into the field "
TCP-Client-Address max
" allows an IP address area to be defined, within
which the IP address of the TCP client may be located.
Now
the TCP Port number, e.g., 40000
The field "own telephone number" can be left blank.
In the field “
Parametrize via
" to cover the need for
Remote parameterization
the option "
GSM-CSD-
Modemverbindung
" has been marked together with the
GSM-Data call number
otherwise the option
"
Local interface
". The decision about which of the two options should be chosen was already made
before in the main window WinPADS (see further above).
If parameterization is effected via the local interface, and if on the SIM card a PIN is active, this PIN
must be entered. For remote parameterization, a PIN need not be entered, as the modem requires
logging on to the GSM network in any case.
Now, with the button
"Set values"
you can start the transmission of the values to the modem.
The transmission of the values to the ComTCPserv modem takes approx.
2 to 2.5 minutes. The completion of complete parameter transmission is
indicated with the message "
Parameterization OK
".
In the event of parameterization through the
local
parameter interface, the
following points must also be dealt with:
Switch off the power supply to the FE260 and disconnect the
parameterization cable from the FE260.
Set the jumper "Mode" to the position "Operation" (upper position).
Make sure that a GSM antenna is connected and that a SIM card has been inserted into the SIM slot
(see Section 7.3.2
.
7.3.5.3 Checking GSM field strength
Before starting a data transfer via the modem, you must ensure that there is adequate reception field strength.
On the display of the EK280, move the cursor in the tab "
Serv.
" to
Interfaces >
"
Terminal interface.
> GSM & GPRS > GSM.L
With the cursor over
GSM.L
, please press the EK280
ENTER
button and wait for approximately 30
to 60 seconds until the field strength percentage is displayed.
i
With a field strength below 50% data transfer issues may be encountered. Adjusting the antenna
position can improve field strength in most cases.