EK280
Application Manual
25
The deviation amount between the two pulse generators, above which a warning is triggered, is editable.
The default is 4 ("maximum number of disturbance pulses") within a 4000 pulse ("pulse window per
disturbance pulses").
This setting can be updated using the EK280 keypad or with enSuite:
a)
On the "
Serv.
" display tab of the EK280 keypad:
Data book >
Inputs
>
L1.I2
Maximum number of disturbance pulses (i.e. 4)
Data book >
Inputs
>
L2.I2
Pulse window per disturbance pulses (i.e. 1000)
With enSuite under "
Parameterize online
" > "
Parameter
":
Data book >
Inputs
>
Limit 1 for monitoring
status input 2 "L1.I2"
Maximum number of disturbance pulses
(i.e. 4)
Data book >
Inputs
>
Limit 2 for monitoring
input 2 "L2.I2"
Factor for pulse window per disturbance
pulses (i.e. 1000)
The maximum number of error pulses is
L1.I2
(i.e. here 4).
The pulse window is
L1.I2
L2.I2
(i.e. here 4
1000 = 4000).