EK280
Application Manual
36
Setting up period length and pulse duration
i
Parametrization of the period length and the pulse duration via the EK280 keyboard is only
possible with software version 2.20 or later.
Older software versions may be programmed using enSuite via "
Parameterize online
" >
"
Parameters
"
and the paths described (see Chapter 6.2.1, 0)
i
The cycle duration and the pulse duration can be set as a multiple of 125 ms for each output.
The cycle duration must always be longer than the pulse duration.
The maximum output frequency is 4 Hz
Examples:
Period
Pulse width
Output frequency
Per.O
in ms
PW.O
in ms
in Hz
2
250
1
125
4
4
500
2
250
2
8
1000
4
500
1
80
10000
40
5000
0.1
When in the corresponding output menu press the button
until
"PerO1"
,
"PerO2"
,
"PerO3"
or.
"PerO4"
is displayed.
Press the ENTER
button. The actual parameterized value flashes.
Move the cursor to the digits using the
or
arrow keys and update them using the
or
arrow
keys to set the desired period.
Press the ENTER button to confirm the value setting. Input can be canceled using the ESC key.
When in the corresponding menu press the button
repeatedly until
"PW.O1
",
"PW.O2"
,
"PW.O3"
or "
PW.O4"
" is displayed.
Press the ENTER
button. The actual parameterized value flashes.
Move the cursor to the digits using the
or
arrow keys and update them using the
or
arrow
keys to set the desired period.
Press the ENTER button to confirm the value setting. Input can be canceled using the ESC key.
Setting up access permissions for the output parameters:
i
Parameterization of access authorizations for the output parameters via the EK280 keyboard
is not possible!
Parameterization may be done with enSuite in
"Parameterize online" > "Parameters" >
"Outputs" > "Output 1" to Output 4"
.