
EK280
Application Manual
137
c) Configure message transmission
With enSuite change to sub-menu "
SMS
" > "
Settings
"
You can define up to 10 SMS messages, change to the related sub-menu "
SMS 1”
up to
"SMS 10”
.
After you changed EK280 parameters activate "
Transfer changes to device
" at the menu bar in enSuite.
d) Configure individual parameters
To transmit a message as email of fax you have to configure abbreviated numbers (different for each
mobile service provider).
Use the enSuite menu "
Read and set single parameters
”
i
If your mobile service provider is not shown please contact your IT department.
SMS
Definition
Event
EK280 event, at occurrence the message will be transmitted. Within enSuite, press the
button and select a status, a unique event or a regular event from the list shown.
NoRcv
0 = no conn. (SMS is not active; will not be sent to any recipient)
1 = Dest 1 or 2 (SMS will be sent only to the first recipient which is reachable)
2 = Dest 1 and 2 (SMS will be sent to both recipients)
LayNo
SMS layout number in the range 1
– 15 (see a))
Iface
Interface 2 = serial interface or 3 = internal modem, where the GSM modem is connected.
Rcv1, 2
Receiver number related to EK280 phone book (see b))
Way1, 2
0 = message will be sent as SMS
1 = message will be sent as email
2 = message will be sent as fax
Delay
Delay of transmission in minutes since event occurs.
PrTyp
7 = short SMS
in case of recipient is not able to display messages with more than 160
characters. The message may be split into multiple short messages.
8 = long SMS
in case of recipient is able to display concatenated messages with more
than 160 characters.
Address
Definition
2:739
(if modem
connected to serial
interface)
3:739
(if internal modem)
Abbreviated numbers for email gateway. Known numbers:
Telecom-D1: 8000
Vodafone-D2: 3400
E-Plus: 7676245
O2: 6245
2:73A
(if modem
connected to serial
interface)
3:73A
(if internal modem)
Abbreviated numbers for fax gateway. Known numbers:
Telecom-D1: 99
Vodafone-D2: 99
E-Plus: 1551
O2: 329