EK280
Application Manual
132
Designation
Modbus_Master_
TaskList_ …
Meaning
Address Value Content
...MdbRegRWMode RW-Mode
12:8C7
3
3: Write-FC16
...MdbStartAdr
Modbus-Adr.
13:8C5
309
5:210_1
T.Mes - Temperature
– measured
value [°C]
...MdbNoReg
Disp.
Register
13:8C6
2
2 registers
...MdbRegRWMode RW-Mode
13:8C7
3
3: Write-FC16
...MdbStartAdr
Modbus-Adr.
14:8C5
311
5:310
C - Conversion factor
...MdbNoReg
Disp.
Register
14:8C6
2
2 registers
...MdbRegRWMode RW-Mode
14:8C7
3
3: Write-FC16
...MdbStartAdr
Modbus-Adr.
15:8C5
313
8:310
K - K-value, 1/K = supercompressibility
ratio factor (Fpv)2
...MdbNoReg
Disp.
Register
15:8C6
2
2 registers
...MdbRegRWMode RW-Mode
15:8C7
3
3: Write-FC16
...MdbStartAdr
Modbus-Adr.
16:8C5
315
7:311_1
p.F - Pressure substitute value [bar]
...MdbNoReg
Disp.
Register
16:8C6
2
2 registers
...MdbRegRWMode RW-Mode
16:8C7
3
3: Write-FC16
...MdbStartAdr
Modbus-Adr.
17:8C5
317
6:311_1
T.F - Temperature substitute value [°C]
...MdbNoReg
Disp.
Register
17:8C6
2
2 registers
...MdbRegRWMode RW-Mode
17:8C7
3
3: Write-FC16
...MdbStartAdr
Modbus-Adr.
18:8C5
319
14:314
N2 - Nitrogen content [%]
...MdbNoReg
Disp.
Register
18:8C6
2
2 registers
...MdbRegRWMode RW-Mode
18:8C7
3
3: Write-FC16
Table 12: Extract from the preprogrammed tasks in the Modbus task list
The parameterized trigger event must take place for communication to start. For testing communication, the
parameter 8:D71 can be set with the brief designation "TestC" to 1 on the device under link 8. The link is then
started as a test. Otherwise there will be a wait until the parameterized trigger event takes place.