65
Installation Manual
Inverter / Whole Home
3.3.5.5. WHOLE HOME
3.3.5.5.1. AUTOMATIC TRANSFER SWITCH
For whole home configurations, make sure an automatic transfer
switch is installed. If off-grid, the maximum load must not exceed the
inverter rating otherwise the inverter will turn off and the loads will
not be backed up until load is reduced to max-rated output of inverter.
Refer to the connection instructions and wiring diagrams provided
with the automatic transfer switch, and see Appendix 5.3, PowerPod 2
Wiring Diagram with ATS.
Once the Automatic Transfer Switch has been wired, take a
photo within the PowerTools app and press 'Next' to move on
to the next step.
Back-up Load
BMS
Battery