58
Installation Manual
Inverter / CTs
•
The CTs must be placed around the correct wire. They are labeled
CT1 to connect to L1 and CT2 to connect to L2.
•
The CTs must face the correct direction. The "House(K)" side of the
CT must face the main panel and the "Grid(L)" side must face the
meter.
•
CT cable is 10m as default.
•
CT cable can be extended to maximum of 30m, contact support@
electriqpower.com for additional support.
3. Route the other end of the CT through the CT port and insert the
4-Pin terminal at the inverter as shown below.
4. After all the wiring connected, close the wiring distribution box,
ensure waterproof and moisture-proof and sealed well.
5. *Important*
Mark CTs wire connections if removing connector
to route cable through conduit or remove excess wire length. See
image below. L1 is the two left side connections (white wire on
the left and black wire on the right) and L2 is the two right side
connections (white wire left and black wire right).
CT Connection